A Balancing Act: Air Balance is an important part of HVAC maintenance

When it comes to HVAC, no news is good news for restaurant facility managers. When you start hearing chatter about the building being hot and humid, drafty, smoky or uncomfortable, you know a problem has already taken root. It’s like a piano being out of tune. In addition to unhappy customers and employees, comfort issues are indicators of energy inefficiency within a system and air balance issues. So, what can facility managers do to prevent comfort and energy threats?

Identifying Common Problems

“Facility managers need to be trained on air balance and push it to their service contractors,” recommends Jeff Dover, resource manager at RFMA.

A good place to start is to gain a foundational understanding of building pressure and common HVAC deficiencies along with following seven easy steps to bring your restaurant back into tune. Most importantly, learn how to look for negative building pressure. Remember, the goal is to stay slightly positive in building pressure.

There are three methods to identify negative building pressure. The first and most reactive method is to monitor signals that your building is negative. These signs are hot/cold spots, entry doors that are hard to open, poor smoke capture, humidity, condensation dripping from diffusers and drafts.

Second, you can measure the building pressure yourself or with the help of your service contractor by using a pressure reading tool such as an anemometer to get a ballpark pressure reading. The third and most accurate method is to hire an air balance firm to check the facility’s building balance once a year. If comfort-related issues or a negative building pressure reading are observed, then an air balance needs to be scheduled.

Investigating the Cause

What causes a building to become negative or unbalanced? The usual offenders are equipment deficiencies, improper preventative maintenance programs, and adjustment errors such as kitchen staff fiddling with thermostats or service contractors opening or closing dampers.

 Here are 10 example deficiencies you or your service contractors should be on the lookout for:

  1. Exhaust fans in poor condition
  1. Supply air leaking above ceiling
  1. OA dampers improperly installed
  1. Exhaust fans not sealed to curb or hinged correctly
  1. Dirty compartment/coil in the RTU
  1. Tops of diffuser not insulated
  1. Filters improperly sized for hoods
  1. MUA not operating properly
  1. Dirty indoor/outdoor filters
  1. Worn/broken belts

Achieving Air Balance in HVAC

Once you’re ready to bring a facility back into tune, there are seven easy steps to complete. These steps may be completed by the facility manager alone, but are more likely in partnership with a service contractor. To get started, pull out the facility’s previous balance report to use as a base line for data.

One Principal Engineer at a hamburger fast food chain overseeing thousands of locations explains how her team uses the air balance report to get started with troubleshooting comfort issues.

“The reports really are my first line of defense when someone says ‘Hey, my store is cold/hot/humid,’ she points out. “The first thing I do is pull out the TAB report and see what it says. I look at the punch list and ask was anything wrong? Not fixed? It helps when I have to remotely assess or diagnose problems.”

7 Steps to HVAC Balance

Whether the previous air balance report has been reviewed or not, proceed to the following steps:

  1. Ask the onsite restaurant managers what the complaints are from employees and customers.
  1. Turn on all HVAC equipment.
    • Verify thermostats are set to “FAN ON”
  1. Check building pressure with the flame test in different areas around the restaurant (Figure 3)
  1. Observe smoke capture
    • Is the hood in the correct overhang position?
    • Are there drafts along the cook line?
  1. Check for common comfort issues (hot/cold spots, entry doors that are hard to open, poor smoke capture, humidity, condensation dripping from diffusers and drafts).
  1. Inspect the equipment.
    • Are the filters clean?
    • Are the belts in good condition?
    • Are the exhaust fan wheels clean?
  1. Determine an intervention plan.
    • If some preventative maintenance actions and/or repairs need to happen, start with the service contractor.
    • If equipment is inoperable, have it repaired or replaced.
    1. If the preventative maintenance actions are in order and the problems persist, call in a certified air balance company that has experience with restaurants like yours.
Facility managers need to trust that their service contractors will notify them of airflow-related issues. Those technicians are out on the roofs and looking at the HVAC system components more than anyone else. If the restaurant has negative pressure or other out-of-tune symptoms, the service contractor needs to inform the facility manager right away. After all, you want your customers and employees to continue singing your praises. 
Air Balance in HVAC

Air Balance Basics for Existing Facilities

We understand the concept of the “band-aid approach” whereby you find a quick cover-up to a problem without actually investigating the root of the it.  This concept applies frequently to Facility Managers or Building Owners wrestling with HVAC emergencies being caused by negative building pressure. They tackle issues such as condensation, hot/cold spots, humidity, odor, and difficult to open doors with “band-aids”. These “band-aids” are in the form of increased air conditioning, dehumidifiers, wet floor caution signs, door mechanisms, air fresheners, apologizing to patrons, comping customers’ bills, and so on.  This is understandable when you’re managing 80+ facilities, all with problems that stretch far beyond just HVAC.  However, it comes with a cost of spending a lot of time, money, energy, and reputation just to have the issues continuing to come back.  While balanced airflow is not a tangible product, the consequences of an unbalanced building are very perceptible.

Facility Managers are ready to de-mystify their HVAC issues by understanding the root causes.  Use the air balance basics below to recognize when an issue is airflow related.

What does it mean to have a balanced airflow?

Think of financial statements with income listed in one column and expenses in the other.  Much like a budget, you want incoming cash coming to be equal to or greater than cash going out. You typically want the air going into a building to be slightly greater than the air going out.  Similarly, think of a balanced scale.  In the graphic below, air is being drawn out of the building by exhaust fans at a rate of 4000 CFM (cubic feet per minute). This is to remove heat and smoke from kitchen cooking appliances and foul air from the restrooms. Air is also being introduced into the building through an outside air fan, at a rate of 4500 CFM. This is to provide fresh breathing air for the occupants and to replace the exhausted air.  The result is a slightly positive building pressure of 500 CFM (4500 – 4000 = 500), which signifies a balanced airflow.  Conversely, if air coming into the building is slightly less than the air leaving the building, then you have a negative building pressure, which is the frequent culprit of many HVAC problems.

Which brings us to a crucial pairing to the air balance concept.  That is if balanced airflow is peanut butter, then a performance test is the jelly.

What is an air test & balance service?
 

Air balance testing is the process of measuring HVAC airflow performance.  Once tested, the systems are then adjusted, or balanced, so the air brought into a building is slightly greater than the air being pulled out of the building.  The benefit for testing and balancing being a combined service is explained by Rob Falke, President of the National Comfort Institute, “This [positive] pressure condition can be designed, but to be sure it actually happens requires air diagnostic testing.  However, it’s hard to say how great the positive pressure reading in the building will be. It depends on how tight (or leaky) the envelope of the building is, and what other pressure generating forces exist, including the wind, appliances, exhaust fans, and the stack effect of the building.”  The result is a comfortable, healthy indoor environment with an HVAC system that is optimized to perform efficiently.